EBSILON®Professional Online Documentation
In This Topic
    Component 70: Evaporator with Steam Drum
    In This Topic

    Component 70: Evaporator with steam drum


    Specifications

    Line connections

    1

    Condensate inlet

    2

    Saturated steam outlet

    3

    Flue gas inlet

    4

    Flue gas outlet

    5

    Drain / Blow Down

    Drain / Blow Down

    6

    Logic input for pump output (optional connection)

     Auxiliary lines for calculation:

    H6

    Water outlet pipe out of drum (saturated to mildly sub cooled)

    H7

    Water outlet pipe out of pump ( Forced circulation)

    H8

    Inlet into drum (two-phase mixture)

     

    General       User Input Values       Characteristic Lines       Physics Used       Displays       Example  

     

    General

    Saturated M2 is determined via M2=(Q87-M5*(H5-H1) ) / (H2-H1-CN*DH) (for derivation see section on Physics used), which results from the setting of the pinch point respectively k*A. This is an important statement because some modeling errors result from an over-determination of mass flow, when the user tries to enforce M2 via component 1 or 33.  

    Or in other words, the setting of the pinch point respectively k*A gives the saturated steam mass flow M2.

     

    However, for M2 a user-entry of a starting value M2N is necessary in the design case. This should lie in the range of the expected steam production. This starting value should not be 0. After the design calculation, the start value entered for M2N is replaced by the calculated nominal value.

     

    In the case of this component, the design via an ”effectiveness” factor is possible. It refers to the theoretically possible maximum heat exchange (for an infinitely large heat exchanger surface area). Thus an effectiveness of 0.8 means that 80 percent of the theoretically possible heat is exchanged.

    Pressure drop limitations in off-design (Extras --> Model Options--> Calculation -->Relative pressure-drop maximum) :
    As the pressure drop rises quadratically with the mass flow, pressure drops that are significantly too high can quickly arise in the event of a transgression of the nominal mass flow. These will then cause phase transitions and convergence problems. For this reason, pressure drop limitations have been installed.


     

    Pin for Pump Power: 

    There is now an optional Pin 6 where the pump power is output. Depending on the desired level of detail of the modeling, a mechanical shaft, an electric line or a logic line can be connected.

    When connecting a shaft, the isentropic efficiency of the circulating pump can be entered in specification value ETAIN and the motor can be modelled separately. Otherwise, the efficiency of the motor should also be considered in ETAIN.

    The component only writes the power on Pin 6. When connecting a shaft and electric line respectively, default values are then used for frequency, voltage, current type, and phase (unless the setting of default values on shafts and electric lines has been disabled by the respective model option). If required, however, the desired values can be set by means of a start value (Component 33).

    View:

    Also for this component there has been a modification in design:

    Flag FTAPPN allows the user to specify whether the feed water temperature is specified outside the component or whether the approach temperature is entered.

     

    A kernel expression can be used as an alternative to the adaptation polynomial. The control is effected via the Flag FADAPT.

     

    Specification of the surface area for designing heat exchangers

    Usually, heat exchangers are designed in Ebsilon by specifying the terminal temperature differences or temperatures to be achieved. In an iterative process, the transferred amount of heat and the product of heat transfer coefficient and surface area (k*A) characteristic for the heat exchanger are calculated from this. Its nominal value KAN then serves to calculate the temperatures in off-design calculations. It is not necessary to know the individual values k and A here.

    In the case of the components ECO/Evaporator/Superheater (exponents, Component 61), Duplex heat exchanger (Component 62), and Evaporator with steam drum (Component 70), however, the off-design behaviour is defined by exponents of heat transfer coefficients AL12 and AL34. As k can be calculated from it, the heat exchanger surface area A is available as well.

    This has been used to implement a design calculation via the specification of the surface area. It is, however, essential to correctly specify the nominal values for the heat transfer coefficients AL12N and AL34N, which had only an effect on the partial load behaviour before to implementation of AN (area).

    For the Evaporator with steam drum (Component 70), AL12N (used only for area calculation) has been newly implemented as a specification value, as it was not required before (because Al12N>>AL34N for the evaporator).

    The specified surface area AN is only used for the design calculation to determine KAN from it. In the off-design calculation KAN is then used for the calculation.

     

    Pinch point violations in the case of heat exchangers   see Heat Exchanger General Notes:

    Up to release 10.0, a pinchpoint violation was only determined subsequently in partial load, i.e. KA was calculated for the respective load case and from this the transferred heat quantity and then it was checked whether this heat quantity can be transferred at all at the correct temperature level. Since in the case of evaporation or condensation the temperature remains constant despite heat input or heat removal, there are cases where heat transfer is not physically possible despite the overall balance being correct. In this case, an error message was issued in Ebsilon.

    The calculation has now been changed in such a way that the transferred heat quantity is reduced as far as it is still physically possible, with the minimum pinch point
    can be set in a default value PINPMIN. This results in a correspondingly reduced KA.
    The user is informed of this by a warning message ("KA reduced to avoid pinchpoint violation") and can then adjust the part-load characteristic curve or the part-load exponent for KA accordingly so that the warning no longer occurs. The advantage, however, is that one gets a physically possible result in any case.

    Furthermore, at the end of the calculation there is a check if there is a pinch point violation due to curved course of Q(T) (caused by significant changes of cp depending on the temperature). This can be verified by dividing the heat exchanger into individual sections.
    This case can occur, for example, when on the hot side the cp at the inlet is significantly smaller than at the outlet (for example, steam that has a cp of about 2 kJ/kgK at high superheat, but more than 5 just above the boiling line). This means that this steam provides more heat at a lower temperature level than at a high one. At appropriately low degrees, this can be a limitation on the amount of heat transfer that is possible.
    The QT diagrams take into account the non-linearity (curvature of the curves) in areas without phase change.

     

    The flag FSPEC (deprecated) has been divided into two flags: 

    Note:

    When loading a model that was created with Release 11 (or older), the corresponding values for FSPECD, and FIDENT are determined from the value of the flag FSPEC, and
    FSPEC is set to “void” (-999). The model then calculates the same result values. If required, however, the flag FSPEC can still be used as well.

    To remove ambiguity, the terms “primary side” and “secondary side” respectively have been replaced bycold side” and “warm side” in the input screens. The cold side (previously “primary”) is the flow from Pin 1 to Pin 2 that is heated. The warm side (previously “secondary”) is the flow from Pin 3 to Pin 4 that gives off the heat.

     

    Effectiveness Method

    The effectiveness method for the design is available for the Evaporator with Steam Drum (Component 70) . In analogy to other heat exchangers, this option is selected via the flag FSPECD=0.
    In the case of Components 25, 26, 27, 51, 55, 61, 70, 124, and 126 a calculation of the effectiveness in the context of the heat exchanger calculation is effected for other design methods as well (however, not in identification mode).
    REFF is the ratio of the actual heat transferred to the theoretical maximum in case of infinite size of the heat exchanger surface.

    A result value REFF has been implemented for this. In the design case, the calculated effectiveness is also stored in specification value EFF when the reference values are taken over.

     

    Note on Component 70 :

     

    Design in the Case of Concurrent Flow see Heat Exchanger General Notes:

    The heat exchanger (Components 70) it is possible to carry out a design via the upper and lower terminal temperature difference also in the case of concurrent flow.

    Flag FDQLR

    In Release 13, you can use the FDQLR flag to define how DQLR (factor for modeling heat losses) should be interpreted.   

    Note on mixtures as working fluid:

    In addition to the boiling temperature TSAT, this component also displays the dew point temperature TTAU as result value. In the case of mixtures as working fluid, the two temperatures may be different. 

    Note about the result values:

    Performance factor RPFHX

    The quotient from the current value for the heat transfer capability k*A (result value KA) and the k*A expected in the respective load point due to the component physics and characteristic lines respectively (result value KACL) serves to assess the condition of a heat exchanger.

    The quotient KA / KACL is displayed as result value RPFHX.


    User Input Values

    FSPECD

    Calculation method in design-case

    Like in Parent Profile (Sub Profile option only)

    Expression
                     

    =0: Effectiveness given as EFF
    =2: Specification of pinch point PINPN
          Specification of the upper terminal temperature difference 
          Temperature difference between the two streams: Outlet side of heat-flow and outlet side of the heated stream    
    =8: Specification of steam production M2 (externally),
          specification of the outlet enthalpy of the cold flow as enthalpy H“ (saturated steam)
    =9: specification of the heat exchanger surface

    FIDENT

    Component identification (only in off-design)

    Like in Parent Profile (Sub Profile option only)

    Expression

    =0: No identification mode, in off-design the steam generation and flue gas outlet temperature are calculated

    =2: M2 given externally in all load cases, KA calculated

    =4: Outlet temperature of hot stream (T4) given externally in off-design, KA calculated
    Note: An identification via the specification of T2 (steam outlet temperature) does not make sense in the case of this component as the outlet condition in this component is always saturated steam, and the outlet temperature is thus defined by the pressure.

    FCIRC

    Circulation method

    Like in Parent Profile (Sub Profile option only)

    Expression

    =0: Natural circulation
    =1: Forced circulation

    EFF

    Effectiveness

    AN

    Heat transfer area (nominal)

    FTAPPN

    Flag for specification of approach temperature in design 

    Like in Parent Profile (Sub Profile option only)

    Expression

    =0: By specification value TAPPN

    =1: T1 given externally

    TAPPN

    Approach temperature difference (nominal)
     

    TAPPN = Tsat(P-drum) - T(Economizer-exit) 

    for H(ECOexit) in the design case applies {

        if TAPPN > 0.01  then { H(Economizerexit) = H(Tsat(Pdrum) -TAPPN) }

        if TAPPN <=0.01 then { H(Economizerexit) = from Economizer-heat balance }

        }

    for H(Economizerexit) in the off-design case applies {

        H(Economizer-exit) = from Economizer-heat balance

        }

    FDP12RN

    Water side pressure drop method

    Like in Parent Profile (Sub Profile option only)

    Expression

    =1: absolute : calculated by DP12N=DP12RN
    =2: relative :   calculated by DP12N=P1N*DP12RN

    DP12RN

    Pressure drop of internal circulation (nominal) [absolute or relative to P1] 

    DP12N is the pressure loss, which must be compensated by a circulation pump

    For a natural circulation boiler, DP12N is set to 0.

    FDP34RN

    Gas side pressure drop method

    Like in Parent Profile (Sub Profile option only)

    Expression

    =1: absolute : calculated by DP34N=DP34RN
    =2: relative :   calculated by DP34N=P3N*DP34RN

    = -1: P4 given from outside

    DP34RN

    Pressure drop line 34 (nominal) [absolute or relative to P3]

    FDQLR

    Heat loss handling

    Like in Parent Profile (Sub Profile option only)

    Expression

    =0: Constant  (DQLR*QN in all load cases)
          DQLR refers to the design value QN (which equals the heat quantity given off by the hot flow in the design case) in all load cases, i.e. it has a constant 
          value in all load cases.
          If, however, this value exceeds 10 percent of the heat quantity given off by the hot flow, the heat loss will be limited to this value, and a warning will
          be output.
    =1: Relative to actual heat input (DQLR*Q34)
          DQLR refers to the heat quantity given off by the hot flow. If the corresponding warning is ignored, losses of more than 10 percent can be modelled
          here too.

    DQLR

    Heat loss (relative to the heat transferred)

    FDRAIN

    Handling of blow down

    Like in Parent Profile (Sub Profile option only)

    Expression

    =0: Blow down flow rate given by specification value M5

    =1: Blow down fraction given by specification value M5M2

    =2: Blow down given externally

    =3: Blow down  mass flow given by function EDRAIN

    M5

    Blow down  mass flow (absolute)

    M5M2

    Blow down  mass flow  (relative to M2)

    (related to the saturated steam mass flow)

    M5=M5M2*M2

    EDRAIN

    Function for blow down mass flow               

     

    ETAIN

    Isentropic efficiency of the circulation pump

    (no characteristic line used:  ETAI=ETAIN)

    CN

    Circulation number of the drum

    CN= M6/M2

    M6=Water mass flow from the drum to the evaporator inlet

    FVOL

    Cartload pressure drop

    Like in Parent Profile (Sub Profile option only)

    Expression

    =0: Only depending on mass flow

           DP/DPN = (M/MN)**2

    =1: Depending on mass and volume flow

           DP/DPN = V/VN*(M/MN)**2

    =2: constant pressure drop (equal nominal value)
           DP = DPN

    FMODE

    Calculation mode

    Like in Parent Profile (Sub Profile option only)

    Expression

    =0: Global

    =1: local off-design (i.e. always off-design mode, even when a design calculation has been done globally)

    =2: special local off-design (Special case for compatibility with the earlier Ebsilon-versions, should not be used in new models, because the results of the real  
          off-design calculations are not always consistent)

    = -1: local design

    FFLOW

    Direction of flow, see Heat Exchanger General Notes:

    Like in Parent Profile (Sub Profile option only)

    Expression

    =0: Counter Current flow

    =1: Concurrent flow

    =2: Cross flow

    NROW

    Number of rows (for cross flow)

    NPASS

    Number of passes (for cross flow)

    FARR

    Arrangement of passes (input for cross flow)

    Like in Parent Profile (Sub Profile option only)

    Expression

    =0: Counter Current flow

    =1: Concurrent flow

    AL12N

    Cold side heat transfer coefficient (used only for area calculation)

    AL34N

    Hot side heat transfer coefficient line 3 to 4 (nominal)

    EX34

     

    Mass flow exponent of  AL34

    AL34= AL34N*(M3/M3N**EX34)* (1 - (TM34N-TM34)*5E-4/°K)

    FADAPT

     

    Flag for using the adaptation polynomial ADAPT/ adaptation function EADAPT

    Like in Parent Profile (Sub Profile option only)

    Expression

    =0: Not used and not evaluated

    =1: Correction for k*A [KA = KAN *K/KN* polynomial]

    =2: Calculation of k*A [KA = KAN * polynomial]

    =1000: Not used, but ADAPT evaluated as RADAPT (Reduction of the computing time)

     

    = -1: Correction for k*A [KA = KAN * K/KN * adaptation function]

    = -2: Calculation of k*A [KA = KAN * adaptation function]

    = -1000: Not used, but EADAPT evaluated as RADAPT (Reduction of the computing time)

    EADAPT

    Adaptation function for KA

    FFU

    On-/Off switch

    Like in Parent Profile (Sub Profile option only)

    Expression

    =0: Heat-exchanger off (no heat transfer, but pressure losses)

    =1: Heat-exchanger active

    PINPMIN

    Minimum value for the pinch point (KA is reduced automatically if the pinch point would fall below this value)

    PINPN

    Pinch point (nominal): 

    T4-Tsat(P7) 

    with P7=P1+DP12N
     

    Please note that only FFLOW = counter current flow is allowed only for the
    calculation mode FMODE=GLOBAL where PINPN is used

    FSPEC (deprecated)

    Specification combi switch (deprecated)

    Like in Parent Profile (Sub Profile option only)

    Expression

    = -999: unused (FSPECD and FIDENT used instead)

    old values:

    =0: Forced circulation, user specifies EFF in design
    =1: Natural circulation, user specifies EFF in design

    =10: Forced circulation, user specifies the pinch point-temperature PINPN in design

    =11: Natural circulation, user specifies the pinch point-temperature PINPN in design

    =20: Forced circulation,  M2 is specified (e.g. by component 33) in design

    =21: Natural circulation, User specifies M2N, which determines M2, in off-design

    =30: Forced circulation,  heat transfer area (nominal) AN given in design

    =31: Natural circulation, heat transfer area (nominal) AN given in design

    KAN                          

    Heat transfer coefficient * area (nominal) , Design Heat Transfer Capability

    QN                            

    Generated heat flow

    M2N                         

    saturated steam mass flow
    in the design case: starting value for the internal iteration for calculating M2

    in off-design: saturated steam mass flow rate (nominal)

    M3N                         

    Hot side mass flow (nominal)

    TM34N                    

    Medium temperature of flue gas (nominal) TM34N=(T3N+T4N)/2

    V1N                         

    Specific volume at point 1 (nominal)

    V3N                         

    Specific volume at point 3 (nominal)

    P1N                         

    Pressure at point 1 (nominal)

    P3N                         

    Pressure at point 3 (nominal)

     

    The identification value that is marked in blue is a reference quantity for off-design mode. The actual off-design values refer to these quantities in the equations used.
     

    Generally, all inputs that are visible are required. But, often default values are provided.

    For more information on colour of the input fields and their descriptions see Edit Component\Specification values

    For more information on design vs. off-design and nominal values see General\Accept Nominal values

     

    The saturated steam production is determined by an iteration procedure. M2N is taken as start value, which should have the same order of magnitude as M2 and M2N. Both quantities should not differ by  a factor of more than 3-5.

     


    Heat Transfer

    TM34   = 0.5*(T3+T4)

    FK2=(1-.0005*(TM34N-T34N))*(M3/M3N)**EX34

    1 / KN  = 1/ AL34N

    1 / K     = 1/(AL34N*FK2) 

     KA / KAN = K / KN 

     


    Physics Used

    Equations

     

    All cases

     

    if FDP12RN=relative, then {DP12N=P1*DP12RN}                                        else {DP12N=DP12RN}

    if FDP34RN=relative, then {DP34N=P3*DP34RN}                                        else {DP34N=DP34RN} 

     

     

    Design case (Simulation flag: GLOBAL = design case AND FMODE = design case)

     

    Condition: FFLOW = counter current

    PH8=PH6=P5=P2=P1

    T2=T5=TH6=TH8=fsat(P1)

    T1= T2-TAPPN

    H1=f(P1,T1)

    H2=fsat(P2,T2,X=1)

    H5=fsat(P5,T5,X=0)

     

    SH6  = f(PH6,TH6)

    PH7=PH6+DP12N

    SH7 = f(PH7,SH6)

    DHS = H7S H6

    DH  = DHS/ETAIN

    HH7  = H6 + DH

    T7  = f(P7,H7)

     

    P4  = P3 - DP34N                                         

    T4=T7+PINPN

    H4=f(P4,T4)

    M4=M3

    Q3=M3*H3

    Q4=M4*H4

    QN= Q3-Q4

    Q87=(Q3-Q4) *(1-DQLR)

     

    Determination of M2 and QPUM

     

    {

    M2*H2-M1*H1+M5*H5-QPUM=Q87

    M1=M2+M5

    QPUM= DH*MH6

    MH6 = M2*CN

    }

     

    M2=(Q87-M5*(H5-H1) ) / (H2-H1-CN*DH)

     

    MH8=MH7=MH6

     

    QPUM= DH*MH6

    QH7=M7*H7

    }

     

    DTLO = T4 TH7 (for FFLOW = counter current)

    DTUP = T3 TH8 (for FFLOW = counter current)

     

    LMTD = (DTUP - DTLO)/(ln(DTUP) - ln(DTLO))

    KAN = DQ/LMTD

    KAN*LMTD =  MH8*H8 MH7*H7     

    KAN*LMTD = (M3*H3 - M4*H4)*(1 - DQLR)

     

     

    Off-design case (Simulation flag: GLOBAL = off-design case or FMODE = off-design case)

     

    TOL =  0.00001

    if FVOL= without, then {

    F1   = (M1/M1N) ** 2     

    if FMODE=1,    then F1=1.0

     

    F3   = (M3/M3N) ** 2

    if FMODE=1,    then F3=1.0

    }

     

    if FVOL= with, then {

    F1    = V1/V1N*(M1/M1N) ** 2

    if FMODE=1  then F1=1.0

     

    F3    = V3/V3N*(M3/M3N) ** 2

    if FMODE=1,   then F3=1.0

    }

     

    PH8=PH6=P5=P2=P1

    T2=T5=TH6=TH8=fsat(P1)

    T1=f(P1,H1)

    H2=fsat(P2,T2,X=1)

    H5=fsat(P5,T5,X=0)

    SH6  = f(PH6,TH6)

    PH7=PH6+DP12N*F1

    SH7 = f(PH7,SH6)

    DHS = SH7 HH6

    DH  = DHS/ETAI

    HH7  = HH6 + DH

    TH7  = f(PH7,HH7)

     

    P4  = P3 - DP34N*F2                                        

    M4=M3

     

    if FMODE = off-design, use KAN and characteristic line, then {

      Marking1

      TM34   = 0.5*(T3+T4)

      FK2=(1-.0005*(TM34N-T34N))*(M3/M3N)**EX34

      KN  = 1/ AL34N

      K  = 1/(AL34N*FK2)

    }

     

    if FMODE = off-design: use KAN, no characteristic line, then { K  = KN}

     

    KA=KAN*K/KN

    Iteration1{

      H4 = (Q3 Q87/(1-DQLR) )/M4

      T4 = f(P4,H4)

     

      DTLO = T4 TH7 (for FFLOW = counter current)

      DTUP = T3 TH8 (for FFLOW = counter current)

      DTLO = T4 TH8 (for FFLOW = concurrent flow)

      DTUP = T3 TH7 (for FFLOW = concurrent flow)

      LMTD = (DTUP - DTLO)/(ln(DTUP) - ln(DTLO))

      QQ = KA * LMTD

      DQQ_1 = DQQ

      DQQ   = Q87 - QQ

     

      regula - falsi method {

        Size = (Q87 Q87_1)/(DQQ - DQQ_1)

        for iteration step 1: Size of the last global iteration step

        Q87X  = Q87  - DQQ * Size

        Q87_1 = Q87

        Q87   = Q87X

      }

     

      DQ = |DQQ /((Q87+QQ)*.5)|

    if DQ < TOL, then end iteration 1

                          else continue the iteration

    }

     

    KA*LMTD =  MH8*HH8 MH7*HH7

    KA*LMTD =  (M3*H3 - M4*H4)*(1 DQLR) 

    For FMODE = off-design, use KAN and characteristic line go to Mark 1, till convergence occurs

     

    Determination ofM2 and QPUM

     

    {

    M2*H2-M1*H1+M5*H5-QPUM=Q87

    M1=M2+M5

    QPUM= DH*MH6

    MH6 = M2*CN

    }

     

    M2=(Q87-M5*(H5-H1) ) / (H2-H1-CN*DH)

     

    M1=M2+M5

    MH6 = M2*CN

    QPUM= DH*MH6

    M7=M6

    QH7=MH7*HH7

     

     


     

     

    Results

    Performance Short Name Dimension

     Heat given to cold stream (incl. heat from pump and to drain)

    Q21 kW
     Transferred heat QT kW
     Heat delivered from hot side flow                           Q34 kW
     Performance factor heat transfer RPFHX -
     Heat Transfer
     Heat transfer coefficient *area KA kW/K
     Heat transfer coefficient K W/m2K
     Heat transfer area A m2
     Mean log temperature difference DTM K

     Lower terminal temperature difference 

    DTLO

    K

     Upper  terminal temperature difference DTUP K

     Alpha number 34 (operation)

    AL34 W/m2K
    KA according to component specific off design behaviour KACL kW/K
    Calculated effectiveness (-actual heat transfer / theoretical maximum in case of infinite size) REFF -
    Part Load

    Relative steam mass flow (Ratio of current steam production to steam production in the design case)

    M2M2N -

    Relative hot side mass flow (Ratio of the current exhaust gas mass flow to the exhaust gas mass flow in the design case)

    M3M3N -
    Peripheral Results -
    Circulation pump power QPUMP kW
    Volume flow at cold side inlet VM1 m3/s
    Volume flow at hot side inlet VM3 m3/s
    Steam quality (X) at cold side outlet

    X2

    -

    Heat transfer to flow 12 up to intermediate point Q12IP kW
    Temperature at flow 12 at intermediate point T12IP °C
    Temperature difference between flow 34 and flow 12 at intermediate point DTIP K
    Result of ADAPT / EADAPT RADAPT -
    Saturated liquid enthalpy or max (HSAT,H1) HLS kJ/kg
    Boiling temperature TSAT °C
    Dew point temperature TDEW °C
    Boiling pressure PSAT bar
    Saturated liquid enthalpy or max (SSAT, S1) SLS kJ/kgK

    Component Displays 

    Use option 1 or 2 in case of forced circulation, options 3 to 5 in case of natural circulation.

    Display Option 1

    Display Option 2

    Display Option 3

    Display Option 4

    Display Option 5

    1

    Example

    Click here >> Component 70 Demo << to load an example.