Line connections |
||
1 |
Flue gas inlet |
|
2 |
Flue gas outlet |
|
3 |
NH3-inlet |
General User Input Values Characteristic lines Physics Used Displays Example
Component 86 simulates a denitrogenization plant (SCR). Here, the fraction of nitrogen oxide (NO, NO2) is reduced in the flue gas by using ammonia (NH3) or a mixture containing ammonia. The scope of this reduction is determined by three characteristic lines.
The first characteristic line CRNO1 describes, how the fraction of the remaining nitrogen oxide (NOX2/NOX1) changes depending on the flue gas mass flow. This characteristic line refers to the nominal mass flow determined in the design calculation.
The second characteristic line CRNO2 describes, how the fraction of the remaining nitrogen oxide changes when the supply of ammonia is increased. The reference point of this characteristic line is the stoichiometric minimum of the ammonia quantity M3MIN, which is needed for the desired conversion (i.e. not the nominal mass flow!). This characteristic line needs to be defined only for values > 1. Caution: In case of this characteristic line the y-values must cover the entire possible range, because the program here searches the x-value for a given y. Especially, it should go asymptotically to infinity for small values of M3/M3MIN.
The third characteristic line CRNO3 describes the effect of the temperature on the fraction of the remaining nitrogen oxide. This characteristic line is not normalized, i.e. the temperatures must be entered directly.
In the design case the outlet concentrations of NOx and NH3 must be specified by NOXN und NH3N. The necessary quantity of ammonia is then calculated.
In off-design mode there are two calculation possibilities set through the flag FSPEC:
In both the cases, the input values of the flue gas (mass flow, pressure, temperature as well as the material composition) on line 1 must be specified. On line 3, NH3 must be entered in the composition; moreover, pressure and temperature must also be specified. The program calculates the properties of the flue gas coming out (line 2).
Pressure drop limitations:
As the pressure drop rises quadratically with the mass flow, pressure drops that are significantly too high can quickly arise in the event of a transgression of the nominal mass flow. These will then cause phase transitions and convergence problems. For this reason, pressure drop limitations have been installed.
(See: Model Settings -> Simulation -> Calculation)
The component considers the following reactions, which take place in the catalyst at 300 - 400 °C in the presence of oxygen:
4 NO + O2 + 4 NH3 --> 4 N2 + 6 H2O
2 NO2 + O2 + 4 NH3 ---> 3 N2 + 6 H2O
FCON |
Flag for interpreting the given concentrations (NOXN, NOXT, NH3N, NH3MAX) Like in Parent Profile (Sub Profile option only) Expression = 1: Mole fraction at reference O2 concentration = 2: Normalized mass fraction at reference O2 concentration The difference between FCON=1 and FCON=2 is the fact that for FCON=2 you have to specify some kind of "density" for the pollutant fraction, i.e. mass of pollutant per volume of flue gas (therefore the dimension mg/Nm³). If you divide this density by the density of the pure pollutant, you get the corresponding volume fraction. In the implementation, the case FCON=2 is traced back to FCON=1, using a constant density of 0.759629 kg/m³ for NH3 and 2.05204 kg/m³ for NOx (independent of NOSPL). |
NOXN |
Outlet-NOX-concentration (nominal) This value is used only for the design calculation |
FSPEC |
Flag for operation type Like in Parent Profile (Sub Profile option only) Expression = 1: NOXT given, M3 calculated = 2: M3 given from outside, NOX calculated at the outlet |
NOXT |
NOX-reference-concentration (in off-design) This value is used only for the off-design calculation |
NH3N |
NH3-concentration at the outlet (nominal) This value is used only for the design calculation |
NH3MAX |
Maximum NH3-concentration at the outlet A warning message is given if this concentration is exceeded |
TMIN |
Minimum temperature for NOX-separation |
TMAX |
Maximum temperature for NOX-separation |
DP12N |
Pressure drop within flue gas (nominal) |
FMODE |
Calculation mode design /off-design Expression =0: GLOBAL =1: Local off-design i.e. always off-design mode, even when the model is calculated in the design mode. |
RNON |
NOX-reduction NOX2/NOX1 (nominal) |
RNO1N |
Nominal reduction for characteristic line 1 |
RNO2N |
Nominal reduction for characteristic line 2 |
RNO3N |
Nominal reduction for characteristic line 3 |
NH3V |
Relative NH3-mass flow M3N/M3min (nominal) |
M1N |
Inlet flue gas mass flow (nominal) |
M3N |
Ammonia mass flow (nominal) |
V1N |
Specific volume at the inlet (nominal) |
The identification value marked in blue is the reference value for the off-design mode. The actual off-design values refer to the values used in the equations.
Generally, all inputs that are visible are required. But, often default values are provided.
For more information on colour of the input fields and their descriptions see Edit Component\Specification values
For more information on design vs. off-design and nominal values see General\Accept Nominal values
RNO |
Calculated reduction coefficient |
RNOXO2 |
NOX concentration at the outlet translated to reference O2 concentration, depending on FCON as molar or normalized mass fraction |
RNH3O2 |
NH3 concentration at the outlet translated to reference O2 concentration, depending on FCON as molar or normalized mass fraction |
M3MIN |
stoichiometric minimum value for the ammonia supply (quantity required for the reaction if the entire ammonia reacted and no residual ammonia remained in the exhaust gas) |
M3M3MIN |
ratio M3 to M3MIN |
LNH3 |
absolute NH3 slip (NH3 mass flow at the exhaust gas outlet): |
LRNH3 |
relative NH3 slip (NH3 mass flow at the exhaust gas outlet in relation to the NH3 supply): Also when using 2-phase fluid or binary mixture at connection point 3. |
RCRNO1 |
value calculated from characteristic line CRNO1 |
RCRNO2 |
value calculated from characteristic line CRNO2 |
RCRNO3 |
value calculated from characteristic line CRNO3 |
Characteristic line 1, CRNO1: Effect of the flue gas mass flow on the NOx-reduction NOX-Removal (NOX2/NOX1in mol%) = f(M1/M1N) |
X-axis 1 M1/M1N 1st point |
|
Characteristic line 2, CRNO2: Effect of the ammonia mass flow on the NOx-reduction NOX-Removal (NOX2/NOX1 in mol%) = f(M3/M3MIN) |
X-X-axis 1 M3/M3MIN 1st point |
Characteristic line 3, CRNO3 : Effect of the flue gas temperature on the NOx-reduction NOX-Removal (NOX2/NOX1 in mol%)= f(T1) |
X-axis 1 T1 1st point |
All cases |
||
|
P2 = P1 DP12
M2= M1 + M3
H2 = ((H1+DH_REAK)*M1+(H3-DH_VERD)*M3)/M2
DH_REAK: Reaction heat of reactions 1), 2) DH_VERD: Heat of evaporation of NH3 |
|
Design case (Simulation flag: GLOBAL = Design case and FMODE = GLOBAL) |
||
|
Pressure drop P2 = P1 DP12N
Energy balance H2 = ((H1+DH_REAK)*M1+(H3-DH_VERD)*M3)/M2
DH_REAK: Reaction heat of reactions1), 2) DH_VERD: Heat of evaporation of NH3
Mass balance M2= M1 + M3
Calculation of the reduction
Input: Concentrations of flow 1 Default Nox-reference = NOXN Default NH3-reference = NH3N Calculation: Concentrations of flow 2 and mass flow 3 as per 1) 4 NO + O2 + 4 NH3 = 4 N2 + 6 H2O 2) 2 NO2 + O2 + 4 NH3 = 3 N2 + 6 H2O 3) NH3 = NH3N 4) NOX=NOXN 5) Split NO/NO2 remains intact
Mass flow 3 (minimum) as per 1) 4 NO + O2 + 4 NH3 = 4 N2 + 6 H2O 2) 2 NO2 + O2 + 4 NH3 = 3 N2 + 6 H2O 3) NH3 = 0 4) NOX=NOXN 5) Split NO/NO2 remains intact
Ratio VNH3=M3/M3MIN
RNO = NOX(Flow 2)/NOX(Flow 1) (in mol%)
RNO1N from characteristic line 1 with M1/M1M = 1
RNO2N from characteristic line 2 with VNH3
RNO3N from characteristic line 3 with T1=T1N in limits TMIN/TMAX |
|
Off-design (Simulation flag: GLOBAL = Off-design or FMODE = Local Off-design) |
||
|
Pressure drop V1: Specific volume of flow 1 DP12 = DP12N*(M1/M1N)**2*(V1/V1N) P2 = P1 DP12
Energy balance H2 = ((H1+DH_REAK)*M1+(H3-DH_VERD)*M3)/M2
DH_REAK: Reaction heat of reactions 1), 2) DH_VERD: Heat of evaporation of NH3
Mass balance M2= M1 + M3
Calculation of reduction ------------------------------------------------------------------------------ IF FSPEC = 1 THEN ------------------------------------------------------------------------------ Input: Concentrations of flow 1 Default Nox-reference = NOXT Default NH3-reference = NH3MAX Calculation: Concentrations of flow 2 and mass flow 3 according to 1) 4 NO + O2 + 4 NH3 = 4 N2 + 6 H2O 2) 2 NO2 + O2 + 4 NH3 = 3 N2 + 6 H2O 3) NH3 = NH3MAX 4) NOX = NOXT 5) Split NO/NO2 remains intact
Mass flow 3 (minimum) according to 1) 4 NO + O2 + 4 NH3 = 4 N2 + 6 H2O 2) 2 NO2 + O2 + 4 NH3 = 3 N2 + 6 H2O 3) NH3 = 0 4) NOX = NOXT 5) Split NO/NO2 remains intact
Maximum ratio VNH3MAX=M3/M3MIN
RNO = NOX(flow 2)/NOX(flow 1) (in mol%)
RNO1 from characteristic line 1 with M1/M1M
RNO3 from characteristic line 3 with T1 in limits TMIN/TMAX
RNO2 = RNO2N*(RNO/RNON)/((RNO1/RNO1N)*(RNO3/RNO3N))
VNH3 from characteristic line 2 with RNO2
ITERATION 1 START -----------------------------------------------------------
Input: Concentrations of flow 1 Default NOX-reference = NOXT Default VNH3 Calculation: Concentrations of flow 2 and mass flow 3 according to 1) 4 NO + O2 + 4 NH3 = 4 N2 + 6 H2O 2) 2 NO2 + O2 + 4 NH3 = 3 N2 + 6 H2O 3) NH3 = fromVNH3 4) NOX = NOXT 5) Split NO/NO2 remains intact
RNO = NOX(flow 2)/NOX(flow 1) (in mol%)
RNO1 from characteristic line 1 with M1/M1M
RNO3 from characteristic line 3 with T1 in limits TMIN/TMAX
RNO2 = RNO2N*(RNO/RNON)/((RNO1/RNO1N)*(RNO3/RNO3N))
VNH3 from characteristic line 2 with RNO2
IF RNO2 constant THEN
ITERATION 1 END ------------------------------------------------------------------------------ IF FSPEC = 2 THEN ------------------------------------------------------------------------------ NOX = NOXT
ITERATION 2 START
Same algorithm as for FSPEC = 1 but with
1) NOX variable 2) M3actual as function of NOX 3) Iteration according to REGULA-FALSI by varying NOX M3actual = M3
ITERATION 2 END
------------------------------------------------------------------------------- FSPEC END -------------------------------------------------------------------------------
V1: Specific volume flow 1
DP12 = DP12N*(M1/M1N)**2*(V1/V1N)
|
|
Display Option 1 |
Click here >> Component 86 Demo << to load an example.