Line connections |
||
1 |
Condensate inlet |
|
2 |
Feed water outlet |
|
3 |
Extraction /Heating steam inlet |
|
4 |
Secondary condensate inlet |
|
5 |
Vent / Exhaust gas |
|
6 |
Additional heating steam |
|
7 |
Heating water |
|
8 |
Bypass steam |
General User Input Values Physics Used Displays Example
Component 63 is a component for simulating the different operation and control conditions of the feed water tank or the deaerator, respectively.
Component 63 simulates the operating conditions that are set as default by means of the variable FSPEC:
Condition on connection point 2 is always identified by state H'(P2). This also applies if the energy balance of feed water tank / deaerator can not be closed, because for example the enthalpy of the heating media is too small. An error message "Energy balance violated" then appears.
If no additional heating steam is used for operating condition 1 in off-design operation, PMIN (or analogue TMIN) is to be assigned to 0.01 (minimum pressure permitted).
Component 9 feed water tank/deaerator 1:
This component simulates the feed water tank/deaerator just like component 63 with the following differences:
component 9 only has connections 1-5:
M3 is ALWAYS calculated from the energy balance
Some options, available in component 63, for heating media and control methods can not be considered in component 9.
In this component, the output of the nominal values M3N, M5N, M6N, and M7N was supplemented. However, they are not used within Ebsilon but are only intended to be used by the user in expressions and scripts.
FMODE |
Calculation mode Expression =0: Global =1: Local off-design =-1: Local design |
|
FSPEC |
Flag for possible operating conditions Like in Parent Profile (Sub Profile option only) Expression =1: Set sliding pressure between PMIN and PN, M3 (if P3>= P2) or M6. = 2: always sliding pressure, always set M3 = 3: P2 given internally, M7 calculated and M6 if M7> M7MAX = 4: M3 given, P2 calculated; if> PMAX set M8, if <set PMIN M6 = 5: P2 = P2N (constant), M3 given from outside, set either M6 or M8 = 6: P2 = P8, M3 given externally, set either M6 or M8 = 7: P2 = P3 (sliding pressure), M7 calculated and M3 if M7> M7MAX (see below for more information) |
|
FPT |
Flag for using temperature or pressure values Like in Parent Profile (Sub Profile option only) Expression =0: use of PN, PMIN, PMAX; (TN, TMIN, TMAX values dummies) =1: use of TN, TMIN, TMAX; (PN, PMIN, PMAX values dummies) |
|
PN |
Pressure in the tank (nominal) |
|
PMIN |
Minimum pressure in the tank |
|
PMAX |
Maximum pressure in the tank |
|
TN |
Temperature in the tank (nominal) |
|
TMIN |
Minimum temperature in the tank |
|
TMAX |
Maximum temperature in the tank |
|
M7MAX |
Maximum heating water mass flow (upon reaching M7MAX, the additional heating steam line 6 is opened) |
|
M5 |
Exhaust vapour loss |
|
M3N |
Heating steam mass flow (nominal) |
|
M5N |
Vent mass flow (nominal) |
|
M6N |
Supplementary heating steam flow (nominal) |
|
M7N |
Heating water mass flow (nominal) |
Generally, all inputs that are visible are required. But, often default values are provided.
For more information on colour of the input fields and their descriptions see Edit Component\Specification values
For more information on design vs. off-design and nominal values see General\Accept Nominal values
The various options for FSPEC are described below in more detail.
FSPEC = 1:
with extraction steam or additional heating steam (given extraction pressure from the outside)
FSPEC = 2:
with extraction steam for pure sliding pressure operation
FSPEC = 3:
with heating water and additional heating steam for sliding pressure
if H2MIN < H'(PMIN)
Tank pressure = PMIN and quantity of additional heating steam = 0, quantity of heating water from the energy balance
if H2MIN >= H'(PMIN)
Calculation of the tank pressure, P(Balance) from the energy balance with the heating water quantity = 0 and additional heating steam quantity = 0
FSPEC = 4:
with heating steam and additional heating steam, heating steam pressure determined by PN
if PMIN > P(Balance)
Tank pressure = PMIN and the quantity of additional heating steam from the energy balance as well as the quantity of bypass steam = 0
if PMIN < P(Balance)
Tank pressure = PMAX and the quantity of additional heating steam = 0 as well as the quantity of bypass steam from the energy balance
FSPEC = 5:
with heating steam and/or additional heating steam operating at fixed pressure
if HTEST > H'(PN)
Calculation of the amount of bypass steam from the energy balance, amount of pegging steam = 0
FSPEC = 6:
with heating steam and/or additional heating steam for sliding pressure (specified by bypass steam)
Previously, both mode FSPEC=2 and FSPEC=3 were called “floating pressure“. However, the pressure is taken over from the extraction line (Pin 3) only at FSPEC=2, while at FSPEC=3 it is variable indeed but is calculated by the component itself. Therefore a new mode FSPEC=7 has now been implemented; it has the following properties:
The heating is effected – insofar as it is possible – by the heating water at Pin 7. If this is not possible (no line connected or temperature too low) or insufficient (after the heating water mass flow has reached its maximum value of M7MAX), heating steam from Pin 3 is used for the (remaining) heating.
FSPEC=7: Sliding pressure
All cases:
All cases |
||
|
if FPT=1, then |
|
Operating condition 1 Preheating with extraction steam (Line 3) OR additional heating steam (line 6) |
||
|
P2=PN; (1) if GLOBAL = Off-design, then if H3 < H2, then P1 = P2 ( 3) if IPAD = 0 , then |
|
Operating condition 2 Preheating with extraction steam (line 3) at pure sliding pressure operation |
||
|
P2 = P3 (1) P1 = P2 (3) P4 = P2 (4) P5 = P2 (5) P7 = P2 (16) P8 = P3 (6) T2 = f'(P2) T5 = T2 H2 = f'(P2) (7) H5 = f''(P2) (8) H8 = H3 (9) M5 = M5 (13) M6 = 0 (11) M1 + M3 + M4 + M6 + M7 = M2 + M5 + M8 (10)
|
|
Operating condition 3 Preheating with heating water (line 7) AND additional heating steam (line 6) and sliding pressure |
||
|
if GLOBAL = design, then if DH2MAX < H'(PMIN) then if DH2MIN < H'(PMIN) then if DH2MIN >= H'(PMIN) then } T2 = f'(P2) if H7>H2, then if Kcase = 1, then if Kcase = 2, then
if Kcase = 3 then M1 + M3 + M4 + M6 + M7 = M2 + M5 + M8 (10
|
|
Operating condition 4 Preheating with heating steam (line 3) and additional heating steam (line 6) |
||
|
if GLOBAL = design, then else HMIN = f' (PMIN) if HX2 < HMIN then if HX2 > HMAX then } P3 = P2 (3) T2 = f'(P2) if Kcase = 0, then if Kcase = 1, then } if Kcase = 2, then if H3>H2, then M33 = (M5*(H5-H2)+M1*(H2-H1)+M4*(H2-H4+M7*(H2-H7)/(H3-H2) else
if Kcase = 3, then { } M1 + M3 + M4 + M6 + M7 = M2 + M5 + M8 (10)
|
|
Operating condition 5 Preheating with heating steam (line 3) and/or additional heating steam (line 6) at fixed pressure |
||
|
if GLOBAL = Design, then P3 = P2 (3) if Kcase = 1, then if Kcase = 2, then if Kcase = 3, then |
|
Operating condition 6 preheating with heating (line 3) steam and/or additional heating at specified sliding pressure of the bypass steam (line 8) |
||
|
P2 = P8 (1) T2 = f'(P2) if H3>H2, then M1 + M3 + M4 + M6 + M7 = M2 + M5 + M8 (10) |
|
Operating condition 7 Preheating with heating water (line 4) / heating steam (line 3) - sliding pressure |
||
|
P2 = P3 (1)
M6 = 0 (11) M6 = 0 (11) M8 = 0 (15) M1+M3+M4+M6+M7 = M2+ M5+M8 (10)
|
|
Display Option 1 |
Click here >> Component 63 Demo << to load an example.