EBSILON®Professional Online Documentation
In This Topic
    Component 24: Compressor
    In This Topic

    Component 24: Compressor / Fan


    Specifications

    Line connections

    1

    Inlet

    2

    Outlet

    3

    Shaft

    4

    Control inlet for efficiency (as H)

     

    General       User Input Values       Characteristic Lines       Physics Used       Displays       Example

     

     

    General

    The pressure at the outlet of the compressor must be specified e.g. with the component 33 (start value).

    For Component 24 (Compressor/fan) there is no pressure calculation; here FCHR has been replaced by FSPECH.

     

    Implementing a load-independent mechanical loss (QLOSSM) (see Release 12)

    If both a mechanical efficiency ETAMN and a constant loss QLOSSM are specified, the two are combined as follows:

    The sequence in which the proportional and the constant fraction are considered depends on the direction of the flow of energy.

    Q_gross =( Q_net + QLOSSM) / ETAMN

    The result value QLOSS comprises the entire (load-independent and load-dependent) loss

    QLOSS = Q_gross – Q_net

    The result value ETAM contains both fractions (as in the case of component 6), as ETAM is defined by

    ETAM = Q_net / Q_gross

    If a QLOSSM > 0 is specified, ETAM thus no longer equals ETAMN but is accordingly smaller (by QLOSSM/heat supply).

     

    Logic inlet (Connection point 4) for controlling component properties

    (see also : Editing components  --> Ports)

    To make component properties like efficiencies or heat transfer coefficients (variation quantity) accessible from the outside (for control or reconciliation) it is possible to place the respective value on an auxiliary line as an indexed measured value (specification value FIND). In the component, the same index must then be entered as specification value IPS.

    It is also possible to place this value on a logic line that is directly connected to the component (please see FVALETAI=2, Variation variable ETAIN, Dimension: Enthalpy).
    The advantage is that the allocation is now graphically visible, and errors (e.g. when copying) are thus avoided.

     

    The activation of this logic line can also be made conditional on the mode of calculation. This way, this feature can also be used for designs without having to switch manually all the time.
    For this, the flag FVALETAI features the settings

    This option is available for Components 2, 6, 8, 13, 18, 19, 23, 24, and 94.

    Polytropic Efficiency

    As an alternative to the isentropic efficiency, the polytropic efficiency can now be output too in the case of the compressor. This is done in the specification value ETAPN. The flag FETA serves to select whether the isentropic or the polytropic efficiency is to be used.

    When using the polytropic efficiency, the isentropic efficiency is calculated as well as the result value ETAI and transferred to the specification value ETAIN. This makes it easier to switch over to the isotropic efficiency, saving computing time as the polytropic efficiency requires a complex numerical integration. This makes itself felt in the case of complex physical properties in particular.

    In the reverse case, ETAP is usually not calculated; however, there is a flag FOUTETAP by means of which this calculation can be activated. In this case, the calculated value of ETAP is also transferred to the specification value ETAPN.

     

    Result Value MCORR

    There is now a result value MCORR that specifies which mass flow would flow through the compressor under standard conditions. The calculation is carried out according to https://en.wikipedia.org/wiki/Corrected_flow:

    MCORR = M1 * SQRT(T1[K]/TNORM) / (P1/PNORM)

    with TNORM = 288.15 K and PNORM = 1.01325 bar.

     


     

    User Input Values 

    FSPECH

    Flag for specification of enthalpies and power:

    Like in Parent Profile (Sub Profile option only)

    Expression

    =0: Efficiency Characteristic used

    =11: Efficiency Characteristic used (validable)

    =-1: Power Specification

    =-11: Power Specification (validable)

    =-2: H2 Specification

    FVALETAI

    Validation of the isentropic efficiency

    Like in Parent Profile (Sub Profile option only)

    Expression

    =0: ETAIN used without validation

    =1: (Deprecated) IPS used instead of ETAIN (validable)

    =2: ETAIN given by enthalpy on control inlet 4

    =4: Enthalpy on control inlet 4 used in design, specification value ETAIN in off-design

    =5: Specification value ETAIN used in design, enthalpy on control inlet 4 in off-design

    ETAIN

    Isentropic efficiency (nominal)

    ETAPN

    Polytropic efficiency (nominal)

    IPS

    Index on pseudo measurement point

    ETAMN

    Mechanical efficiency (nominal)

    QLOSSM

    Mechanical loss (constant fraction)

    FCHR

    Char Line type (deprecated)

    Like in Parent Profile (Sub Profile option only)

    Expression

    =-999: unused

    =0:  ETAI/ETAIN=f(M1/M1N)

    =-1: Power specification

    =-2: H2 given

    FMODE

    Flag for calculation mode
    Expression

    =0:   GLOBAL

    =1:   Local off-design

    = -1: Local design

    FADAPT

    Flag for adaptation polynomial / adaptation function

    Like in Parent Profile (Sub Profile option only)

    Expression

    =0: Not used and not evaluated

    =1: correction [ETAI = ETAIN * Char Line * polynomial]

    =2: Replace [ETA I = ETAIN * polynomial]

    =1000: Not used but ADAPT evaluated as RADAPT (Reduction of the computing time)

    = -1: correction [ETAI = ETAIN * Char Line * adaptation function]

    = -2: Replace [ETA I = ETAIN * adaptation function]

    = -1000: Not used but EADAPT evaluated as RADAPT (Reduction of the computing time)

    EADAPT

    Adaptation function

    M1N         

    Mass flow (nominal)

    The parameters marked in blue are reference quantities for the off-design mode. The actual off-design values refer to these quantities in the equations used.

    Generally, all inputs that are visible are required. But, often default values are provided.

    For more information on colour of the input fields and their descriptions see Edit Component\Specification values

    For more information on design vs. off-design and nominal values see General\Accept Nominal values


     

    Results

    ETAI

    Isentropic efficiency

    ETAP

    polytropic efficiency

    ETAM

    Mechanical efficiency (including QLOSSM)

    RHO1

    Specific weight of flue gas at inlet

    VM1

    Volume flow at air intake

    ETANIR

    Used value for nominal isentropic efficiency

    ETACL

    Efficiency due to characteristic

    RADAPT

    Result of ADAPT / EDAPT

    DP

    Pressure difference

    ETAINR

    Used value for nominal isentropic efficiency

    MCORR

    Corrected mass flow

    M1M1N

    Relative cold side mass flow

    ETAETAN

    Relative efficiency

     


     

     

    Characteristic Lines

    Characteristic line 1: Isentropic efficiency ETAI/ETAIN = f (M1/M1N)

         X-axis          1         M1/M1N                      1st point
                            2          M1/M1N                     2nd point
                            .
                            N         M1/M1N                      last point
     
         Y-axis          1          ETAI/ETAIN                  1st point
                            2          ETAI/ETAIN                  2nd point
                            .
                            N         ETAI/ETAIN                   last Point
     


    Physics Used

    Equations

    All cases

     

    P2   from the line 2

    M2 = M1                                                    

    if the medium in the pipe is water/steam, then {

      S1   = f(P1,H1)

      H2S  = f(P2,S1)  }

    else {

      S1   = f(P1,T1)

      T2S  = f(P2,S1)

      H2S  = f(P2,T2S)  }

    DHS  = H2S - H1

    DH   = DHS/ETAI

    H2   = H1 + DH                                        

    T2   = f(P2, H2)

    Q2   = M2 * H2

    H3   = (M2*H2-M1*H1)/(ETAM*M3)      

    V1 = f(P1,T1)

    VM1   = M1*V1  volume flow at inlet

     

    Component Displays

    Display Option 1

    Example

    Click here >> Component 24 Demo << to load an example.