EBSILON®Professional Online Documentation
In This Topic
    Component 152: Electric Compression Chiller
    In This Topic

    Specifications

    Line connections

    1

    Heat source inlet

    2

    Heat source outlet

    3

    Heat rejection inlet

    4

    Heat rejection outlet

    5

    Power inlet

    6

    Condensate outlet

    7

    Logic Inlet

     

    General     User Input Values      Characteristic Lines      Specification Matrices    Physics Used     Example

    General

    With component 152, electric chiller, the user can model the performance and power consumption of a chiller system based upon electrically driven compression chillers. The performance (power consumption) calculation is based on curves. Default curves are available as a collection of curves for specific chiller units which are available on the market. 

    User Input Values 

    FMODE

    Flag to set the calculation mode Design / Off-design

    Like in Parent Profile (Sub Profile option only)
    Expression

    =0:   Global
    =1:   local off-design (i.e. always off-design mode, even when a design calculation has been done globally)
    =-1: local design (i.e. always design mode, even when a off-design calculation has been done globally)

    FFU

    Switch ON/OFF

    Like in Parent Profile (Sub Profile option only)
    Expression

    =0: OFF (heat source inlet = heat source outlet; all other flows = 0)

    =1: ON

    FDES

    Flag to set the chiller design mode

    Like in Parent Profile (Sub Profile option only)
    Expression

    =2:  Outlet temperature T2 set externally

    =4:  Desired outlet temperature T2 given as T2TARGET

    FSIZE

    Flag to set the basis for the unit size

    Like in Parent Profile (Sub profile option only)
    Expression

    =0:  cooling duty MXQC (calculate NUNITS and RLOAD < LOAD)

    =1:  heating duty MXQH (calculate NUNITS and RLOAD < LOAD)

    =2:  from T2, LOAD and NUNITS

    FCOP

    Flag to set the basis for COP (coefficient of performance)

    Like in Parent Profile (Sub profile option only)
    Expression

    =0:  Electrical power (MXQEL) - COP will be calculated relative to cooling duty Q12

    =1:  Cooling COP (MXCOP)

    =2:  Heating COP (MXCOP)

    FOPOD

    Flag to set the operating mode in off-design

    Like in Parent Profile (Sub profile option only)
    Expression

    =2:  Desired outlet temperature T2 set externally (calculate NUNITS and RLOAD < LOAD)

    =4:  Desired outlet temperature T2 given as T2TARGET (calculate NUNITS and RLOAD < LOAD)

    =1:  Set NUNITS and cartload fraction as LOAD

    =3:  Set NUNITS and cartload fraction on logic port 7 as H

    LOAD

    Desired cartload fraction

    T2TARGET

    Desired exit temperature

    NUNITS

    Number of active units

    DP12

    Pressure drop between heat source inlet and outlet

    DP34

    Pressure drop between heat rejection inlet and outlet

    MINLOAD

    Minimum cartload fraction per unit

    T1N

    Nominal inlet temperature of the heat source

    M1N

    Nominal inlet flow of heat source

    M3N

    Nominal inlet flow of heat rejection

    V1N

    Nominal specific volume of heat source

    V3N

    Nominal specific volume of heat rejection

    Q12N

    Nominal cooling duty per unit

    DP12N

    Nominal heat source pressure drop

    DP34N

    Nominal heat rejection pressure drop

    NUNITSN

    Nominal number of units

     

    The parameters marked in blue are reference quantities for the off-design mode. The actual off-design values refer to these quantities in the equations used.

    Generally, all inputs that are visible are required. But, often default values are provided.

    For more information on colour of the input fields and their descriptions see Edit Component\Specification values

    For more information on design vs. off-design and nominal values see General\Accept Nominal values

     

    Characteristic Lines

    CPLCOP :  COP correction = f (Q12/Q12BASE); Q12/Q12BASE is the part load fraction of the cooling cycle

                        1        cooling cycle cartload fraction         1st point
                        2        cooling cycle cartload fraction         2nd point
                        .
                        N       cooling cycle cartload fraction         last point
     
         Y-Axis      1       COP correction factor                        1st point
                        2        COP correction factor                         2nd point
                        .
                        N        COP correction factor                         last point
                     

    CT4MAX:  maximum T4 = f(T1); maximum heat sink outlet temperature as a function of heat source inlet temperature

         X-Axis      1       Heat source inlet temperature           1st point
                          2      Heat source inlet temperature           2nd point
                        .
                        N       Heat source inlet temperature           last point
     
         Y-Axis      1       Maximum heat sink exit temperature    1st point
                        2        Maximum heat sink exit temperature    2nd point
                        .
                        N       Maximum heat sink exit temperature     last point
     

    CT4MIN:  minimumT4 = f(T1); minimum heat sink outlet temperature as a function of heat source inlet temperature

         X-Axis      1       Heat source inlet temperature           1st point
                          2      Heat source inlet temperature           2nd point
                        .
                        N       Heat source inlet temperature           last point
     
         Y-Axis      1       Minimum heat sink exit temperature    1st point
                        2        Minimum heat sink exit temperature    2nd point
                        .
                        N       Minimum heat sink exit temperature     last point
     

     

    Specification Matrices

    MXQC: Q12 = f (T1, T4)

    Cooling duty as a function of heat source inlet temperature and heat sink exit temperature

     

    MXQH: Q34 = f (T1, T4)

    Heating duty as a function of heat source inlet temperature and heat sink exit temperature

     

    MXQEL: Q5 = f (T1, T4)

    Power consumption as a function of heat source inlet temperature and heat sink exit temperature

     

    MXCOP: COP = f (T1, T4)

    Coefficient of performance (COP) as a function of heat source inlet temperature and heat sink exit temperature.  The basis for the COP, i.e. if it is relative to the cooling or the heating duty, has to be specified in the parameter FCOP.

    Physics Used

    Basic Model

    The module carries out mass and energy balances for the two process streams which comprise the heat source and the heat sink. In addition, an overall energy balance provides all relevant duties, such as cooling, heating and electric energy: 

    Warm Side Duty = Cold Side Duty + Electrical Energy

     

    The thermodynamic process internal to the electric chiller is the vapour compression evaporation or heat pump process in which a medium runs through a cycle of evaporation (thereby picking up heat from a heat source at a lower temperature level and cooling the heat source stream from T1 to T2) - compression to a higher pressure level - condensation (thereby rejecting heat a higher temperature level and heating up the heat sink from T3 to T4) - and throttling to a lower pressure level (which reduces the temperature for evaporation).  
    An electric compression chiller consists of one or several heat pump units of which the performance is typically characterized in terms of coefficient of performance (COP).  Depending on the vendor's convention, the COP may either express the ratio of cold side duty to electrical energy (referred to as Cooling COP in component 152) or the ratio of hot side duty to electrical energy (referred to as Heating COP).  If such performance characteristic is available, it is not necessary to model the internal heat pump cycle in detail, and component 152 uses this approach.

    Chiller Performance

    The operation of a compression chiller is characterized by performance maps with boundaries in terms of cold side (heat source) inlet temperature (T1) and the achievable warm side (heat sink) temperature (T4) which is the maximum temperature rise a specific machine can produce. Below diagram shows a typical performance range for an industrial heat pump.

    The permissible boundaries are specified in terms of two characteristic lines, which define the maximum possible T4 (CT4MAX) and the minimal required T4 (CT4MIN) for the unit to function properly, as a function of cold side inlet temperature (T1). Below diagram shows the permissible minimum and maximum hot side exit temperature, corresponding to the above performance characteristics. It is the user’s responsibility to provide sufficient mass flow at the heat sink so that the resulting warm side exit temperature remains within these boundaries. If the temperature boundaries are exceeded, the component will issue a warning. Exceeding T4max means the flow 34 needs to be increased, falling below T4min means flow 34 needs to be reduced.

    A library of heat pump performance characteristics has been included in the Default-Values Database of component 152.  With the command "Load default-values.." in the tab "Basic Properties" the following menu can be activated which lists the default data sets which provide both, specification matrices and corresponding settings for calculation settings, so that the performance data are ready to use. 

    Chiller Setup

    The component can be set up to represent just the chiller units; one chiller unit or any array of equally sized units, of which the number can either be specified by the user, or it can be determined based on a given performance of the chiller unit:

     

    Design Calculation

    Typically the user will specify the cold side duty of the process through inlet temperature (T1), flow rate (M1) and desired exit temperature (T2) of the main inlet stream (e.g. GT inlet air) which can specified through the method FDES to be set externally or defined by input value T2TARGET. While setting up a model, it is the user’s responsibility to adjust warm side flow rate so that the resulting exit temperature (T4) remains within permissible boundaries. The model offers several ways to specify the chiller performance. These are the following performance maps with the parameters cold side inlet temperature T1 and warm side exit temperature T4, in form of two dimensional specification matrices:

    (1) Cold-Side Duty (MXQC:Q12)

    (2) Warm-Side Duty (MXQH:Q34)

    (3) Electric Power Consumption (MXQEL:Q5)

    (4) Warm-Side Coefficient of Performance (MXCOP:COP, FCOP=2)

    (5) Cold-Side Coefficient of Performance (MXCOP:COP, FCOP=1)

    Performance maps (1)-(3) are given in absolute units (kW, BTU/h) and fit the capability of a specific physical unit. Adjustment to a desired heating or cooling duty in design mode will be achieved by calculating the necessary number of units. For using unit specific performance maps (1)-(3) it is required to use two matrices for providing a full balance: either (1) or (2) in combination with either (3) or (4) or (5) .  The respective combination can be defined in the input vales FSIZE (basis for unit size) and FCOP (basis for COP).  If the electrical consumption is calculated directly from the matrix MXQEL (i.e. FCOP = 0), the result value for the coefficient of power RCOP will be based on the cold side duty Q12.

    The calculation flow is as follows: Using T1 and T4 the model looks up performance map (1) or (2) (depending on the specification FSIZE) and looks up performance map (3), or (4), or (5) depending on FCOP. With that the electric power consumption can be calculated, and by means of balance the other corresponding duty.

    Performance maps (4) and (5) are dimensionless. These can be used, if no unit specific data of a chiller are available. The model contains a reasonable default performance map. The user has to select FSIZE = 2 and define the number of units in operation with the specification value NUNITS, and based on the default map the unit will be sized in terms of nominal cooling duty Q12N. In such case the calculation procedure is as follows: Depending which process side (cold or warm) is fully specified in terms of inlet temperature, outlet temperature and flow rate, the model calculates the respective duty.  Using T1 and T4, the model looks up the corresponding performance map for COP and determines the electrical load.  The overall energy balance determines the remaining duty and respective inlet/exit temperature.  Dividing the resulting total cooling duty by the specified number of units produces the size per unit.

     

    Equations:

     

    Q34 = Q12 + RPOWR

     

     

    FSIZE = 0:   Q12 = RNUNITS * RLOAD * Q12BASE

     

     

                      Q12BASE = MXQC(T1,T4)

          

     

    FSIZE = 1:  Q34 = RNUNITS * RLOAD * Q34BASE

     

     

                     Q34BASE = MXQH(T1,T4)

     

     

    FSIZE = 2:  Q12 = M1* (H1 - H2*) = LOAD * NUNITS * Q12BASE with H2* calculated at T2 before condensate drain

     

     

    FCOP = 0:  RPWR = RNUNITS * MXQEL(T1,T4)/ CPLCOP(RLOAD)

     

     

    FCOP = 1:  RPWR= Q12/RCOP;  RCOP = CPLCOP(RLOAD) * MXCOP(T1,T4)

     

     

    FCOP = 2:  RPWR= Q34/RCOP;  RCOP = CPLCOP(RLOAD) * MXCOP(T1,T4)

     

     

    Off-Design Calculation

    In off-design, the unit size (Q12BASE or Q34BASE) and maximum available number of units (NUNITSN) are fixed.  The user may choose to completely switch off the chiller via FFU, or select the off-design operating mode from the methods drop-down list FOPOD. 

    Operation with Temperature Control (FOPOD = 2,4)

    The desired exit temperature from the chiller may be defined in the input value T2TARGET or set externally, and the calculation will determine the number of chiller units that have to be in operation with a resulting cartload level (RLOAD) that comes closest to the desired part load level (LOAD).   If however the desired temperature cannot be reached with the maximum available number of units (NUNITSN) at the defined load level, an error message will be generated.

    Operation with Load Control (FOPOD = 1,3)

    If operated with load control, the user specifies the number of units in operation with the input value NUNITS that has to be smaller or equal NUNITSN, and the part load fraction either with input LOAD or as value for enthalpy on the logic line of port 7.  The latter setting allows for combination with an external controller to achieve a specific target.  

    The mass and energy balances are closed using the set of performance maps defined in the design case. 

    Pressure drop on the cold side and warm side are evaluated based on a quadratic law DP = DPdesign*V/Vdesign*(M/Mdesign)2 

     

    Component Displays

    Display Option 1

    Display Option 2

    Example

    Click here >> Component 152 Demo << to load an example.