EBSILON®Professional Online Documentation
In This Topic
    Component 11: Generator
    In This Topic

    Component 11: Generator


    Specifications

    Line connections

    1

    Power inlet at Shaft

    2

    Power outlet at terminals

    3

    Logic line (Control line inlet ) for frequency (as M), H2-pressure or voltage (as P),Efficiency (as H), power factor cos phi (as NCV)

     

    General       User Input Values       Displays

    General

    Component 11 is used to model a generator.

    In the design mode, the generator efficiency must be specified.

    In the Generator, the nominal value of the generator efficiency can also be specified as enthalpy on the logic inlet (Pin 3) instead of in the specification value ETAGN, allowing this value to be controlled too. The flag FETAGN serves to define which specification is to be used.

    The off-design performance is defined by characteristic lines. These characteristic lines consist of

    These characteristics provide the dependency of the generator efficiency on the given mechanical shaft power.


    For the efficiency of the generator, an EbsScript function in the specification field EADAPT can be used (see Release 9, Kernel expressions, chapter 3.2).

    In the standard value database, the values for the generator efficiency and the interdependence of load and cos phi have been updated. Data records for the magnitudes 83 and 277 MW are available. By default, the 83 MW values are loaded. The curves used up to Release 8 are also available. When loading models generated with Release 8, the values are not changed.


    Double lookup of characteristic fields:

    To ensure consistency between the design and off-design calculations, characteristic lines have to go through point (1,1). This is not difficult for simple characteristic lines. For a characteristic field, i.e. a set of characteristic lines depending on one parameter, not all characteristic lines of the set can go through (1,1). The corresponding prerequisite is here: one characteristic line in the set has to go through (1,1), and this must be the one that corresponds with the design value of the parameter.
    As the characteristic field is not always present in this form, a manual (e.g. Excel-based) conversion used to be necessary in certain cases. For reasons of simplification, the double lookup has therefore been introduced, initially for the generator (Component 11).
    The advantage is that the user no longer has to care if and where the value (1,1) occurs in their characteristic field. The trick is that the characteristic field is activated twice for the off-design calculation: once with the design values and once with the current values. The quotient from both results of the characteristic field is then used as characteristic field factor for the off-design calculation. For this, however, it has been necessary to introduce nominal values for the respective quantities (in the case of the generator for cos(phi), hydrogen pressure, and generator frequency).
    To use this feature with the generator, the flag FCHR has to be set to 2 (“Double lookup (for not normalized characteristics)“).

     

    Logic inlet (Connection point 3) for controlling component properties

    (see also : Editing components  --> Ports)

    To make component properties like efficiencies or heat transfer coefficients (variation quantity) accessible from the outside (for control or reconciliation) it is possible to place the respective value on an auxiliary line as an indexed measured value (specification value FIND). In the component, the same index must then be entered as specification value IPS  (component 11: IPSCOS,IPSH2P, IPSGENF). 

    It is also possible to place these values (measurement points) on a logic line that is directly connected to the component.

    please see
    FCOS=2, Variation variable: COSPHI, Cos(phi), dimension: mass flow on control inlet)
    FH2P=2, Variation variable: H2P, H2-pressure, dimension:  pressure on control inlet)
    FGENF=2, Variation variable: GENF, Frequency, dimension: enthalpy on control inlet

    The advantage is that the allocation is graphically visible, and errors (e.g. when copying) are thus avoided. 

    Specification of Frequency, Current, Voltage, and Phase

    In the generator, the specification values COSPHI (for the power factor) and GENF (for the frequency) as well as the new specification value VOLT (Voltage) are used for specifying these variables.

    For the specification values to be used, the flags FCOS, FGENF, and FVOLT are to be set accordingly.
    In this case, the current is calculated from the output. The positive algebraic sign is used for the phase.

     

    Display Formats :

    Generator: Graphical symbols can be displayed instead of or in addition to the letter “G”. (see Component Displays).

     

    Note for the FCOS / FGENF switches

    If the flags FCOS and FGENF respectively are set accordingly, the specification values COSPHI and GENF will be transferred (as of Release 12) to the electric line.
    As in Release 11 the default setting for these flags was “not used“, no changes occur for these flags.

    For models created with older versions of Ebsilon where the setting “not used” did not exist, an unintended transfer of the power factor and the frequency to the electric line may occur.
    Usually this has no consequences. If, however, start values for mass flow or pressure were used on the shaft and electric line respectively (which was required in former versions
    of Ebsilon), double entries may occur, but these are easy to eliminate by removing the unnecessary specifications.

    Note: Result value RGENFREQ

    From this release this value (RGENFREQ) has the unit frequency - EBSILON standard unit 1 / min. The user can change the display unit to display the frequency in Hz.


    User Input Values 

    FETAGN

    Specification of generator efficiency

    Like in Parent Profile (Sub Profile option only)
    Expression

    Specification of generator efficiency
    =0: By specification value ETAGN
    =2: By enthalpy on control inlet

    ETAGN

    Generator efficiency (nominal)

    FCHR

    Flag for usage of char line

    Like in Parent Profile (Sub Profile option only)
    Expression

    =1: Simple lookup (for characteristics normalized to design parameters)

    =2: Double lookup (for not normalized characteristics)

    FCHRX

    x-Values  of the Characteristic Lines
    =1: Ratio of prevailing shaft power to nominal shaft power Q1/Q1N
    =2: Ratio to the electrical power Q2/Q2N

    FCOS

    Handling of power factor (cos phi) to be used for characteristics and result values

    Like in Parent Profile (Sub Profile option only)
    Expression

    =0: Specification value COSPHI is used
    =1: (Deprecated) Pseudo measurement point given by IPSCOS as power factor
    =2: (Deprecated) use phase on control line inlet 3 to calculate power factor
    =3: Defined by phase on electrical outlet to calculate power factor
    =-1: not used
    =-2: (Deprecated) defined by mass flow on control inlet 3 as power factor

    COSPHI

    Power factor cos phi

    IPSCOS

    Index of the pseudo measurement point for power factor cos phi

    FH2P

    Handling of H2 pressure

    Like in Parent Profile (Sub Profile option only)
    Expression

    =0: Specification value H2P is used
    =1: (Deprecated) Pseudo measurement point given by IPSH2P
    =2: H2 pressure given by pressure on control line inlet 3
    =-1: not used

    H2P

    Hydrogen pressure in the generator casing

    IPSH2P

    Index of the pseudo measurement point for H2 pressure

    FGENF

    Handling of generator frequency-default

    Like in Parent Profile (Sub Profile option only)
    Expression

    =0: Specification value GENF is used
    =1: (Deprecated) defined by generator frequency from measurement point given by IPSGENF
    =2: Frequency given by measurement point on control inlet 3
    =3: Defined by measurement point on shaft inlet
    =-1: not used
    =-2: (Deprecated) defined by enthalpy on control inlet 3

    GENF

    Generator frequency

    IPSGENF

    Index of the pseudo measurement point generator frequency

    FMODE

    Flag for calculation mode

    =0: GLOBAL

    =1: local off-design

    =-1: local design

    FVOLT

    Handling of voltage

    Like in Parent Profile (Sub Profile option only)

    Expression

    =0: Defined by specification value VOLT
    =2: Defined by measurement point on control inlet 3
    =3: Defined by measurement point on electrical outlet
    =-1: not used

    VOLT

    Voltage (on electric line)

    FADAPT

    Flag for adaptation polynomial / adaptation Function

    Like in Parent Profile (Sub Profile option only)

    Expression

    =0: Not used and not evaluated

    =1: Correction factor for characteristics: the value for the generator efficiency determined from the characteristic is multiplied with the value of the adaptation polynomial

    =2: Substitute for characteristic: ETAGN is multiplied with the value of the adaptation polynomial, the characteristic is not used

    =1000: Not used, but ADAPT evaluated as RADAPT (Reduction of the computing time)

    =-1: used result of EADAPT-function as correction factor for characteristics

    =-2: used result of EADAPT-function as replacement factor for characteristics

    =-1000: Not used, but EADAPT evaluated as RADAPT (Reduction of the computing time)

    EADAPT

    Adaptation Function

    Q1N     

    Power at generator inlet (nominal)

    COSPHIN    

    Power factor (nominal)

    H2PN     

    H2 pressure (nominal)

    GENFN     

    Generator frequency (nominal)

    The parameters marked in blue are reference quantities for the off-design mode. The actual off-design values refer to these quantities in the equations used.  

    Generally, all inputs that are visible are required. But, often default values are provided.

    For more information on colour of the input fields and their descriptions see Edit Component\Specification values

    For more information on design vs. off-design and nominal values see General\Accept Nominal values

     

    Characteristic Lines

    Previously, all characteristic lines always referred to

    the ratio of prevailing shaft power to nominal shaft power.

    As, however, many manufacturers have their characteristic lines refer to the electrical power, Ebsilon now allows to use the flag FCHRX to switch over from Q1/Q1N (FCHRX=1) to Q2/Q2N (FCHRX=2).

    Characteristic lines (COSPHI-Characteristic lines)

    Characteristic line 1 : Electrical efficiency  ETAG/ETAGN = f (Qx/QxN,PHI1)

    PHI=COS(PHI)

         X-Axis      1      Qx/QxN                  1st point
                        2       Qx/QxN                  2nd point
                        .
                        N       Qx/QxN                  last point
     
         Y-Axis     1        ETAG/ETAGN         1st point
                        2        ETAG/ETAGN         2nd point
                        .
                        N        ETAG/ETAGN        last point
     

     

    Characteristic line 2 : Electrical efficiency  ETAG/ETAGN = f (Qx/QxN,PHI2)

         X-Axis      1      Qx/QxN                  1st point
                        2       Qx/QxN                  2nd point
                        .
                        N       Qx/QxN                  last point
     
         Y-Axis     1        ETAG/ETAGN         1st point
                        2        ETAG/ETAGN         2nd point
                        .
                        N        ETAG/ETAGN        last point
     

     

    Characteristic line 3 : Electrical efficiency  ETAG/ETAGN = f (Qx/QxN,PHI3)

         X-Axis      1      Qx/QxN                  1st point
                        2       Qx/QxN                  2nd point
                        .
                        N       Qx/QxN                  last point
     
         Y-Axis     1        ETAG/ETAGN         1st point
                        2        ETAG/ETAGN         2nd point
                        .
                        N        ETAG/ETAGN        last point
     

     

    Characteristic line 4 : Electrical efficiency  ETAG/ETAGN = f (Qx/QxN,PHI4)

         X-Axis      1      Qx/QxN                  1st point
                        2       Qx/QxN                  2nd point
                        .
                        N       Qx/QxN                  last point
     
         Y-Axis     1        ETAG/ETAGN         1st point
                        2        ETAG/ETAGN         2nd point
                        .
                        N        ETAG/ETAGN        last point
     

     

    Characteristic line 5 : Electrical efficiency  ETAG/ETAGN = f (Q1/Q1N,PHI5)

         X-Axis      1      Q1/Q1N                  1st point
                        2       Q1/Q1N                  2nd point
                        .
                        N       Q1/Q1N                  last point
     
         Y-Axis     1        ETAG/ETAGN         1st point
                        2        ETAG/ETAGN         2nd point
                        .
                        N        ETAG/ETAGN        last point 
     


    Characteristic lines  2 (H2P-Characteristic lines)

    Characteristic line 6 : Electrical efficiency ETAG/ETAGN = f (Qx/QxN, H2P_1)

    H2P=p(H2)

         X-Axis      1      Qx/QxN                  1st point
                        2       Qx/QxN                  2nd point
                        .
                        N       Qx/QxN                  last point
     
         Y-Axis     1        ETAG/ETAGN         1st point
                        2        ETAG/ETAGN         2nd point
                        .
                        N        ETAG/ETAGN        last point
     

     

    Characteristic line 7 : Electrical efficiency ETAG/ETAGN = f (Qx/QxN, H2P_2)

         X-Axis      1      Qx/QxN                  1st point
                        2       Qx/QxN                  2nd point
                        .
                        N       Qx/QxN                  last point
     
         Y-Axis     1        ETAG/ETAGN         1st point
                        2        ETAG/ETAGN         2nd point
                        .
                        N        ETAG/ETAGN        last point
     

     

    Characteristic line 8 : Electrical efficiency ETAG/ETAGN = f (Qx/QxN, H2P_3)

         X-Axis      1      Qx/QxN                  1st point
                        2       Qx/QxN                  2nd point
                        .
                        N       Qx/QxN                  last point
     
         Y-Axis     1        ETAG/ETAGN         1st point
                        2        ETAG/ETAGN         2nd point
                        .
                        N        ETAG/ETAGN        last point
     

     

    Characteristic line 9 : Electrical efficiency ETAG/ETAGN = f (Qx/QxN, H2P_4)

         X-Axis      1      Qx/QxN                  1st point
                        2       Qx/QxN                  2nd point
                        .
                        N       Qx/QxN                  last point
     
         Y-Axis     1        ETAG/ETAGN         1st point
                        2        ETAG/ETAGN         2nd point
                        .
                        N        ETAG/ETAGN        last point

     

    Characteristic line 10 : Electrical efficiency ETAG/ETAGN = f (Qx/QxN, H2P_5)

        X-Axis      1      Qx/QxN                  1st point
                        2       Qx/QxN                  2nd point
                        .
                        N       Qx/QxN                  last point
     
         Y-Axis     1        ETAG/ETAGN         1st point
                        2        ETAG/ETAGN         2nd point
                        .
                        N        ETAG/ETAGN        last point
     


    Characteristic lines 3 (Generator frequency-Characteristic lines )

    Characteristic line 11-19 : Electrical efficiency ETAG/ETAGN = f (Qx/QxN, GENF_1...9, EBSILON standard unit 1 / min)

    GENF (Hz)

         X-Axis      1      Qx/QxN                  1st point
                        2       Qx/QxN                  2nd point
                        .
                        N       Qx/QxN                  last point
     
         Y-Axis     1        ETAG/ETAGN         1st point
                        2        ETAG/ETAGN         2nd point
                        .
                        N        ETAG/ETAGN        last point

     

     

    Equations

    all cases 

     

    M2*H2 = M1*H1 * ETAGN * f 1(Qx/QxN) * f2(Qx/QxN) * f3(Qx/QxN)

     

     

    Component Displays

    Display Option 1

    Display Option 2

    Display Option 3

    Display Option 4

    Display Option 5

    Display Option 6

    Display Option 7

    Display Option 8

    Example

    Click here >> Component 11 Demo << to load an example.

    See Also