EBSILON®Professional Online Documentation
EBSILON Professional Components / Components - General and Categories / Heat Exchanger / Component 107: Condenser for binary mixtures
In This Topic
    Component 107: Condenser for binary mixtures
    In This Topic

    Component 107: Condenser for binary mixtures


    Specifications

    Line connections

    1

    Cooling medium inlet                  

    2

    Cooling medium outlet                 

    3

    Exhaust steam inlet                   

    4

    Condensate outlet                 

    5

    Secondary condensate inlet                  

    6

    for future use

     

    General       User Input Values       Characteristic Lines       Physics Used       Displays       Example

     

    General

    This component differs from component 7 by using a binary mixture at the inlet on the hot side. Because such a mixture does not have a fixed condensation temperature, but at first the solvent condenses and at lower temperatures eventually also the cooling agent, the outlet temperature of the cooling water can be above the condensation temperature range in the case of this component.

    Flag FSPECPD:

    In Release 13 it is possible specify the design pressure (and also the start value for the internal iteration in off-design) in the component as specification value P3N.
    The specification is controlled via the flag FSPECPD (see "User Input Values").

     

    Flag FDQLR

    It is possible to use the FDQLR flag to define how DQLR (factor for modeling heat losses) should be interpreted.

     

    External Specification of the Pressure of the Auxiliary Condensate

    Since the auxiliary condensate is at the same pressure level as the condensate, it is necessary during modeling to install a control valve or a condensate valve on the auxiliary condensate line in to decrease  the pressure to the Preheater / Heating condenser level.

    To simplify the modeling, there is now a mode “P5 given externally“ that can be set by means of the flag FP5. This mode allows to connect a line with a higher pressure on
    Pin 5. Within the component, the auxiliary condensate is then reduced to the preheater / heating condenser pressure. The result is the same as with an external control valve.

    This mode is the default setting for newly inserted components. For existing models, FP5 is set to “P5=P3“.

     

    Pressure drop limitations in off-design (Extras --> Model Options--> Calculation -->Relative pressure-drop maximum) :
    As the pressure drop rises quadratically with the mass flow, pressure drops that are significantly too high can quickly arise in the event of a transgression of the nominal mass flow. These will then cause phase transitions and convergence problems. For this reason, pressure drop limitations have been installed.

     

    Note about the result values:

    Performance factor RPFHX

    The quotient from the current value for k*A (result value KA) and the k*A expected in the respective load point due to the component physics and characteristic lines respectively (result value KACL) serves to assess the condition of a heat exchanger.

    The quotient KA / KACL is displayed as a result value RPFHX.

     

    Treatment of mixtures: Note about the result values: 

    In the process of the unification of this component with Component 7, an inconsistency when using water/lithium bromide as working fluid was noticed. As no lithium bromide exists in the gaseous phase, this component has to condense pure steam in this case and should therefore behave exactly like Component 7. The reference temperature for specification value DT3S2N should therefore also be the boiling temperature of water. That was not so, in this case the temperature at Inlet 3 was used. This has been corrected. The error message at too high values of DT3S2N now contains information on what the reference temperature is, so that the value can be adjusted accordingly.

    The error message at too high values of DT3S2N contains information on what the reference temperature is, so that the value can be adjusted accordingly.  


     

    User Input Values

    DT3S2N

    Upper terminal temperature difference (nominal)

    FSPECPD

    Design specification for vapour pressure

    Like in Parent Profile (Sub Profile option only)

    Expression

    =0:  Design vapour pressure given by specification value P3N
           (The specification value P3N is used as condenser pressure in the design case and as start value for the pressure calculation in off-design.
           If, additionally, a pressure specification is effected on the line, a double entry will be reported.)

    =1:  Design vapour pressure given externally
           (In the design case, the pressure given on the line will be used as condenser pressure and saved in P3N when the reference values are subsequently
           taken over.
           In off-design, P3N is then used as start value for the pressure calculation. If, additionally, a pressure specification is effected on the line in off-design,
           a double entry will be reported.)

    =-1: Design vapour pressure given externally (in off-design as start value)
            (The pressure given on the line is used as condenser pressure in the design case and as start value for the pressure calculation in off-design. 
            No double entry will be reported due to the specification on the line even if the pressure is defined by the condenser.
            (This case corresponds to the behaviour up to Release 12.)

    P3N

    Steam pressure (nominal)

    DP12N

    Cold side pressure drop, for line 1 to 2 (nominal)

    DP34N

    Hot side pressure drop, for line 3 to 4 (nominal)

    TOL

    Tolerance in energy balance     

    FDQLR

    Heat loss handling

    Like in Parent Profile (Sub Profile option only)

    Expression

    =0: Constant  (DQLR*QN in all load cases)
          DQLR refers to the design value QN (which equals the heat quantity given off by the hot flow in the design case) in all load cases, i.e. it has a constant 
          value in all load cases.
          If, however, this value exceeds 10 percent of the heat quantity given off by the hot flow, the heat loss will be limited to this value, and a warning will
          be output.
    =1: Relative to actual heat input (DQLR*Q354)
          DQLR refers to the heat quantity given off by the hot flow. If the corresponding warning is ignored, losses of more than 10 percent can be modelled
          here too.

    DQLR

    Heat loss to the environment by radiation
    (relative to the radiating current)

    FMODE

    Flag for calculation mode Design/Off-design

    Like in Parent Profile (Sub Profile option only)

    Expression

    =0: global

    =1: local off-design (i.e. always off-design, even if global design mode was selected)

    =2: special local off-design (special case for compatibility with earlier EBSILON®Professional  versions, should not be used in newer models, because the results of the real off-design calculations are not consistent)

    = -1: local design

    FSPEC

    Flag for the setting, which parameters are specified and which have to be calculated (concerns only off-design)

    Like in Parent Profile (Sub Profile option only)

    Expression

    Normal calculation modes (characteristic line or adaptation polynomial is used):

    0: M1=M1N, T2 and P3 calculated (using k*A)
    1: T2 given, M1 and P3 calculated (using k*A)
    2: M1 given, T2 and P3 calculated (using k*A)

    Identification modes (characteristic line and adaptation polynomial are ignored, k*A is calculated from measurement values):

    3: T2 and P3 given, M1 calculated, identification of k*A
    4: P3 given, M1=M1N, identification of k*A
    5: M1 and P3 given, T2 calculated, identification of k*A

    This flag is ignored in the design mode.

    FADAPT

    Flag for using the adaptation polynomial ADAPT / adaption function EADAPT

    Like in Parent Profile (Sub Profile option only)

    Expression

    =0: Not used and not evaluated

    =1: Correction factor for k*A [KA = KAN * carline factor *polynomial]

    =2: Calculation of k*A [KA = KAN * polynomial]

    =1000:Not used but ADAPT evaluated as RADAPT (Reduction of the computing time)

    =-1: Correction factor for k*A [KA = KAN * carline factor *adaption function]

    =-2: Calculation of k*A [KA = KAN * adaption function]

    = -1000: Not used but EADAPT evaluated as RADAPT (Reduction of the computing time)

    EADAPT

    Adaption function

    KAN

    k*A (nominal) - Design Heat Transfer Capability

    M1N           

    Cold side mass flow  (nominal)

    M3N           

    Hot side mass flow (nominal)

    QN               

    Condenser duty (nominal)

    The parameters marked in blue are reference parameters for off-design, which are calculated by EBSILON®Professional  in the design mode. The actual off-design values refer to these parameters in the equations used .

    Generally, all inputs that are visible are required. But, often default values are provided.

    For more information on colour of the input fields and their descriptions see Edit Component\Specification values

    For more information on design vs. off-design and nominal values see General\Accept Nominal values

     

    Characteristic Lines

    There are two characteristic lines, which describe the effect of the primary mass flow or of the secondary mass flow respectively on k*A. The complete correction factor for k*A results from the multiplication of both the influencing factors.

    1. Characteristic line CKAM1  FK1 = f (M1/M1N)
    2. Characteristic line CKAM2  FK2 = f (M3/M3N)
     
    Total: (K*A)/(K*A)N = FK1 * FK2

     

    Characteristic line 1:  (k*A)-Characteristic Line:  (k*A)1/(k*A)N = f (M1/M1N)

         X-axis      1        M1/M1N                 1st Point
                        2        M1/M1N                 2nd Point
                        .
                        N        M1/M1N                 last Point
         Y-axis      1        (k*A)1/(k*A)N          1st Point
                        2        (k*A)1/(k*A)N          2nd Point
                        .
                        N        (k*A)1/(k*A)N          last Point

    Characteristic line 2:  (k*A)-Characteristic Line:  (k*A)2/(k*A)N = f (M3/M3N)

         X-axis      1        M3/M3N                 1st Point
                        2        M3/M3N                 2nd Point
                        .
                        N        M3/M3N                 lastPoint
         Y-axis      1        (k*A)2/(k*A)N          1st Point
                        2        (k*A)2/(k*A)N          2nd Point
                        .
                        N        (k*A)2/(k*A)N          last Point


     

    Physics Used

     

    Equations

    Design case (Simulation flag : GLOBAL=Design and FMODE=GLOBAL)

     

    P2 = P1 - DP12N                                           
    P4 = P3 - DP3N                                            
    P5 = P3                                                         

    M2 = M1                                                      
    M4 = M3 + M5                                             

    T3S = fsat (P3)
    T2 = T3S - DT3S2N
    H2 = H(P3, T3S)                                            

    T4S = fsat(P4)
    T4 = T4S
    H4 = fsat(P4)                                                 
    Q3 = M3*H3
    Q4 = M4*H4
    Q5 = M5*H5
    DQ = (Q3 + Q5 - Q4)*(1-DQLR)
    M1*(H2 - H1) = DQ                                      

    DTL = T4 - T1
    DTU = T3 - T2
    LMTD = (DTU - DTL)/(ln(DTU) - ln(DTL))

    KAN = DQ/LMTD

     

     

    Off-design  (Simulation flag: GLOBAL=Off-design or FMODE=Off-design (local)

     

    F1 = (M1/M1N) ** 2     
    P2 = P1 - DP12N * F1                                   

    F3 = (M3/M3N) ** 2
    P3 = P4 + DP34N * F3                                 
    P5 = P3                                                        

    M2 = M1                                                      
    M4 = M3 + M5                                            


         Fk1   = f (M1/M1N)  from Characteristic Line 1
         Fk2   = f (M3/M3N)  from Characteristic Line 2
         KA = KAN * Fk1 * Fk2          

    Start of the iteration
     

    T4  = fsat(P4)
    H4  = fsat(P4)                                            
    Q12 = (Q3 + Q5 - M4*H4) * (1-DQLR)       
     

    If FSPEC = 0,2,  then{  

                        H2 = H1 + Q12/M2
                        T2 = f(P2,H2) }

    If FSPEC = 1,  then{  T2 from  user input  }

    DTL = T4 - T1
    DTU = T3 - T2
    LMTD = (DTU - DTL)/(ln(DTU) - ln(DTL))
     
    QQ = KA * LMTD
    DQQ = Q12 - QQ
     
    Start of the Regula Falsi Method

    grad = (P4- P4old)/(DQQ - DQQold)
    P4   = P4  - DQQ * grad                           
    End of the Regula Falsi Method

     
    DQ = | DQQ/((Q12+QQ)*.5) |


    If DQ < TOL, then end the iteration

                          else continue the iteration

     

    If FSPEC = 0,  then{

                    M2 = M1 = M1N }                          
     

    If FSPEC = 1,   then{

                    M2 = Q12/(H2 - H1)      }           
     

    If FSPEC = 2,  then{

                    M2 = M1 from the start value setter   }

     

     

    Result values

    Note:

    Like in the simple steam turbine condenser (Component 7), there were the result values DT3S2 and DT4S1 in this component. As for binary mixtures, however, the boiling temperature is not constant, specifying temperature differences for the boiling temperature does not make much sense here. 

    Therefore

    is output for Component 107.

    Attention: If DT3S2 or DT4S1 has been used for Component 107 in an EbsScript, there will now be a compiler error, which can be remedied by renaming to DTUP and DTLO respectively.


    Component Displays

    Display Option 1

    Display Option 2

    Display Option 3

     

    Example

    Click here >> Component 107 Demo << to load an example.