EBSILON®Professional Online Documentation
Calculations / Settings
In This Topic
    Settings
    In This Topic

    Calculation Settings   

    For further information, see

     Global Calculation Mode

    This calculation mode applies to all components of a model. It can be set individually for each profile and is either

    Normally, design calculations take place in the root profile (ID = 0). In the sub-profiles, calculations normally take place in Off-Design mode.

    This calculation mode can be set via:

    • the button Design / Partial Load (light bulb as icon: off: Off-Design/ lit: Design)
    • the model setting (Simulation-->Calculation-->Global Calculation Mode (GLOBAL, 0:Design / 1:Off-Design)
    • EbsScript: by setting the value of the Variable       
      @calcoptions.sim.globalmode (0: Design / 1: Off-Design)
      
    • EbsOpen: by setting        
      Profile.Configuration.Simulation.GlobalCalculationMode(0: Design / 1: Off-Design)
      

    In design mode, the nominal values of a component are calculated and entered or adopted as specification values for the component.
     
    For this purpose, in the general settings under Calculation/General there is a selection box "Accept calculated global design values" with the following setting options:
     

     

     
      - No: The calculated results are not taken over into (accepted) the nominal values.
     
      - Yes: The calculated results are taken over (accepted) into the nominal values.
     
      - Show dialogue box: A message box appears in which again the answer Yes or No can be given.
    The nominal values are shown in blue colour in the component properties dialogue and their name usually ends with an "N" (examples: M3N, P2N, DP12N).

    The components for which a distinction is made between design and off-design mode have a default value FMODE, which is normally set to "Global: 0". This means that the global calculation mode applies to these components.
     
    Other terms for Design are: Nominal load, Design calculation, Design.
    Other terms for Off-design are: Partial load
    Other terms for nominal values are: Reference values, design values

    Local Off Design

    It is possible to exclude individual components from the Global Calculation Mode by setting their value of FMODE to "Local off design".
    They then behave as they would in a Off Design calculation - regardless of the "global calculation mode".

    Local Design

    For most components it is possible to set the value of FMODE to "local design".

    For components where this setting is active, a design calculation is always performed, also independent of the "global calculation mode".

     

    If there are components in this mode in the model, the question is asked in a message box - even after a partial load calculation - whether the nominal values should be taken over.


    It is possible to copy the calculated nominal values into another profile than the current one. For this purpose a selection box appears in which the desired profile can be selected into which the nominal values are to be copied.

    If you tick the checkbox "Copy all default values", not only the nominal values but all default values are taken over, with the exception of FMODE itself. This eliminates the need for manual copying, for example from ETAI to ETAIN for the steam turbine.

    However, this dialogue can also be hidden if you always want to copy the nominal values to the current profile or always to the main profile. For this purpose, there is a selection box "Save calculated nominal values" in the general settings under Calculation/General with the following setting options:

     

         

    The reference profile can be set in the profile dialogue (Data --> Profiles).

    Design and identification

    A design calculation is used to determine the nominal values needed in off-design calculations when using characteristic curves.

    In a calculation where a component is in an identification mode, values specified outside the component are used to determine, for example, the efficiency of this component or its k*A value (heat transfer capability). These specifications are values specified with measured value components or by other means on the connected lines, e.g. also with neighbouring components or also via components connected to the line with logic lines. 

    Such a calculation in identification mode is possible in design as well as in off-design calculations. 

    In such a case, the nominal values of this component are taken over in the design mode and also the identified component value(s) (e.g.: efficiency ETAI is copied to ETAIN for component 6, gradient DT3S2 is copied to DT32SN for component 10, pressure drop DP12 is copied to DP12N or pressure drop DP34 is copied to DP34N for component 10).

    In case of a calculation in the identification mode in the off-design, no values are taken over. The component values to be identified   hier weiter


     

    Matrix Precision

    The solution process of Ebsilon is a matrix solution. This requires the linearization of all dependencies. To take into account influences resulting from non-linearities, a Newton iteration is done afterwards.

    This iteration is considered completely, if the deviation from the previous iteration step is smaller than the specified precision value for all matrix cells. It is recommended to choose a value of 10^(-6) or 10^(-7).

     

    Off-design method for component 10

    Component 10 is the feed water preheater, which consists usually of a de-heating part and a condensing part. At the boundary between these two zones there is the well-known <pinch-point>. EBSILON®Professional offers two methods to carry out off design calculations.

    The simplified method assumes that the separation zone between de-heating part and condensing part is fixed and does not move in off-design mode. This method may result in <pinch-point> problems (too small values) for very low loads (below 50%).

    The second method was published by Prof. Rabek in the sixties and takes into account moving of the separation zone. This method agrees better with reality, but is much more complicated in the calculation.